Warom HRD96 Series Explosion-proof LED Lightings
◆ Explosion protection to EN, IEC
◆ Can be used in Zone 1,2,21,22 Class I, Zone 1,2 Division 1, Groups A, B, C, D
◆ Three enclosure type: 30, 60, 120
◆ Applicable lamp and power (max.120W)
LED : 30W, 60W, 120W
◆ Isolated LED lamp compartment, CC-CV (constant current -constant voltage) power controller compartment and terminal compartment; Wind-convection heat dissipation structure
◆ Low-maintenance due to long service life is up to 100,000 operating hours.
Certified Authentic With Complete Certificate
- Description
- Specification Data
- Technical Parameters
- Photometric Data
- Mounting Type, Mouting Accessories & Spare Parts
Specification Data
Global (IECEx) | IECEx (applied for) |
Gas and dust | Ex db op IIC T6 Gb
Ex tb op IIIC T80℃ Db IP66 |
Europe (ATEX) | ATEX (applied for) |
Gas and dust | II 2 G Ex db op IIC T6 Gb |
II 2 D Ex tb op IIIC T80℃ Db IP66 | |
Certificates | IECEx; ATEX |
Conformity to standards | EN; IEC |
Degree of protection | IP66 |
Ambient temperature | -40℃~+55℃ |
Material | Copper-free Aluminium Alloy, powder coated surface, yellow (RAL1021)
Toughened glass, stands 4J impact |
Weight | 2~5.5kg |
Dimensions | 316x316x118mm |
Lamp specification | LED module, Multiple LED |
Lamp power (W) | 30W, 60W, 120W |
Rated voltage | 220~240V AC 50/60Hz |
Rated luminous flux | 3150~12300lm |
Terminal | 3 x 1.5~4mm2 (L+N+PE) |
Cable entries | M25 x 1.5 |
Available cable outer diameter | Φ10~Φ14 (mm) |