Description
BPY96 Series
Explosion Proof Energy Saving High Efficiency Fluorescent Light Fittings (IIC, tD)
<image>
Application
- Designed for explosive atmospheres Zone 1 and Zone 2;
- Designed for combustible dust Zone 21 and Zone 22;
- Designed for IIA, IIB and IIC groups explosive atmospheres;
- Designed for temperature classifications with T1~T6;
- T5 Bi-pin tube;
- Designed for explosive hazardous locations such as oil refinery, storage, chemical, pharmaceuticals, military industries, etc.
Model Code
BPY 96 – [] x [] [] []
[] – J: With emergency unit
[] – Mounting Types (x: ceiling; g: pendant; b: wall; h:stanchion; f: pole; w: bend)
[] – Each tube power
[] – Tube number
96 – Design No.
BPY – Explosion proof energy saving high efficiency fluorescent light fittings.
Selection Table
Model | Power (W) | Luminous Flux (lm) | Ballast | Lamp Holder |
PBY96-1×14 | 14 | 1050 | Electronic | G5 |
PBY96-2×14 | 28 | 2100 | ||
PBY96-1×21 | 21 | 1750 | ||
PBY96-2×21 | 42 | 3500 | ||
PBY96-1×28 | 28 | 2400 | ||
PBY96-2×28 | 56 | 4800 |
Ordering References
- The lamp is included inside when delivery;
- Only one tube works under emergency conditions.
For example: If need PBY96 explosion proof energy saving high efficiency fluorescent fittings, 2×28 fluorescent tubes, pendant type, with emergency unit, the model shall be “BPY96-2X28gJ”.
Features
- Enclosure is die casted of aluminum alloy with high voltage electrostatic powder coated surface after shot blasting;
- High strength thoughened glass transparent tube;
- Exposed fasteners are of stainless steel with high corrosion resistance properly;
- Steel guards are treated by dip plastic with reliable corrosion resistance;
- T5 Bi-pin fluorescent tube is lamp;
- T5 fluorescent tube with features of high lighting efficiency, long service life (20000h) and good colour rendition (Ra>85);
- Electronic ballast with high power factor cos Φ ≥ 0.95;
- Modular plug-in design only need to open end cover and pull out core to change tubes;
- Light fittings with emergency unit are integrated, which is easy to install and save space;
- Light fittings with emergency unit will automatically shift to emergency lighting model when normal power
- Over charging and over discharging protection circuit inside emergency unit;
- Lamp cavity is of spigot and cementing explosion proof structure, wiring cavity adopts increased safety
- Internal and external earthing bolts ensure reliable earthing;
- Steel pipe or cable wiring.
Technical Parameters
Compliance with: GB 3836.1, GB 3836.2, GB 3836.3, GB 12476.1, GB 12476.5, IEC60079-0, IEC60079-1, IEC60079-7, IEC61241-0, IEC 61241-1;
Rated voltage: Ac 220V;
Lamp: T5 Bi-pin fluorescent tubes (1x14W, 2x14W, 1x21W, 2x21W, 1x28W, 2x28W) G5 lamp holder Electronic ballas;
Ingress Protection: IP66;
Corrosion Resistance: WF1
Cable entries: 2-G1/2″
Cable outer diameter: Φ6mm~Φ10mm;
Charging time: ≤ 24h;
Emergency starting time: ≤ 0.3s;
Emergency lighting duration: ≥ 120min.
Dimensions and Photometry
Type | BPY96 (T5 Fluorescent Tube) | ||||||||||||
Dimension | <image>
|
||||||||||||
Photometric Curve cd/1000lm | <image> |
Outline and Mounting Dimensions
<images>
Model | L1 | L2 |
1×28, 2×28 | 1213 | 1213 |
1×21, 2×21 | 913 | 883 |
1×14, 2×14 | 613 | 583 |
No | Description | Remarks |
1 | Fluorescent light fittings | |
2 | Stud M8 x 155mm | |
3 | Specialized junction box for BPY96 | |
4 | Explosion proof adapter BGJ-G1/2C | |
5 | Flexible conduit NGd-20 x 700C(G3/4M-G1/2M) | Equipped by user |
6 | Bend pipe G1 1/4 | |
7 | Connector | |
8 | Stanchion pole G1 1/2 | |
9 | Explosion proof union BHJ-C(G1 1/2M G3/4M) | Equipped by user |
10 | U Clamp G1 1/2 | Equipped by user |
11 | Clamp G1 1/4 | |
12 | Pole G1 1/2 | |
13 | Fixed plate | Equipped by user |
14 | Mounting Support | |
15 | Steel pipe G1/2 x 240mm | |
16 | Connection bolt G1/2F M8M | |
17 | Steel pipe G1/2 x 300mm | |
18 | Sucker G1/2 | |
19 | Explosion proof union BHJ-C (G1 1/4M-G3/4M) | Equipped by user |
20 | M8 bolt | |
21 | Wall type support |