Description
Descriptions:
The explosion-proof LED emergency power supply is used with explosion-proof LED emergency light fittings. The enclosure of explosion-proof LED emergency light fittings are manufactured in die-cast aluminum alloy with epoxy resin power sprayed on the surface, so that they have food anti-corrosion performance. For ensure the light fittings using life, the emergency power supply built-in inverter and high temperature nickel battery, design separate lightings. Explosion-proof LED emergency light fittings have the function of open circuit (no load) for ensure the personal safety when installation and maintenance.
The explosion-proof LED emergency light fittings can satisfy the requirements in Petroleum, chemical industry, medicine, war industry, food, power plants and other enterprises.
LED Explosion-proof emergency light fittings can be sorted as: bracket lamp, platform lamp and wall lamp.
LED Explosion-proof emergency bracket type lamps can be sorted as: ceiling type, wall sunction type and chain type.
The mounting ways of the LED explosion-proof emergency platform light fittings C-90° are fence type and platform flange type.
The mounting ways of the LED explosion-proof emergency platform light fittings D-25° are fence type and platform flange type.
- There is a feature of good electromagnetic compatibility and it does not cause interference to the system power grid.
- It is not influenced by the voltage fluctuations and can be operated in the wide voltage range 100~240V AC
- There is a good performance of vibration due to the LED is the solid-state light source
- The highest class of flameproof is up to II C
- The degree of protection is up to IP66
Main Technical Data
Certification | Ex mark | Meet the standard
China (CQST Ex) | Ex de II C T6 DIP A21 TA, T6 | GB3836 GB12476 |
Intended use: Can be used in zone 1 and zone 2, Can be used in zone 21 and zone 22
Degree of protection: IP66
Rated voltage: 100 ~ 240V AC 50/60Hz
Rated power: 30W
Recharging time: 24h
Emergency starting time: 0.1 (S)
Emergency illuminating time: > 90 (min)
Power factor: > 0.98
Ambient temperature: -40°C ≤ Ta ≤ 50°C
Terminal: 2.5mm2, PE terminal: 2 x 10mm2
Cable entry: 3 x G3/4″
Outside diameter: ϕ8-11.5mm
Order specifications
Mounting circuit diagram for emergency light fittings
Outline dimensions